Trox vav terminal units

VAV terminal unit type TVR with an Easy controller

Easy controller, Compact controller

Easy controller, Compact controller

VAV terminal unit, variant TVR-D-FL

Construction with acoustic cladding and flange

VRU-D3-M-B_img_01psd.png

Universal controller VRU-D3-M/B TR

Universal controller (VARYCONTROL)

TROX UNIVERSAL controller,

TROX LABCONTROL controller

doc_graphic_000009.png

Tested to VDI 6022

Conforms to VDI 6022

TVR_Easy_img_02psd.png

doc_graphic_000009.png

TVR

For various standard applications

Optional equipment and accessories

General information

Application

Special features

Nominal sizes

Construction

Parts and characteristics

Attachments

Accessories

Useful additions

Construction features

Materials and surfaces

Galvanised sheet steel construction

Powder-coated construction (P1)

Stainless steel construction (A2)

Variant with acoustic cladding (-D)

Standards and guidelines

Fulfils the hygiene requirements of

Closed blade air leakage:

Maintenance

Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Related Products

TVR_gc_01ai.png

Schematic illustration of the TVR

① Effective pressure sensor

③ Double lip seal

④ Control components, e.g. an Easy controller

The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate. The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL). For most applications, the setpoint value comes from a room temperature controller. The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

Nominal sizes 100 – 400 mm
Volume flow rate range 34 – 7591 m³/h or 10 – 2108 l/s
Volume flow rate control range (unit for dynamic effective pressure measurements) Approx. 10 – 100% of the nominal volume flow rate
Volume flow rate control range (unit for static effective pressure measurements) Approx. 15 to 100% of the nominal volume flow rate
Minimum differential pressure

Up to 117 Pa (without circular silencer)

Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.

The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".

Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates q vmin and q vmax .

Volume flow rate ranges and minimum differential pressure values

The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. Sufficient static differential pressure (Δ pstat,min ) must be ensured for all operating conditions and for all controllers . The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.

Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – Easy (potentiometers)
Attachment: Easy

NS qv [l/s] qv [m³/h] Δpstmin [Pa] Δqv [±%]
100 10 34 1 1 1 2 16
100 38 136 12 14 16 19 9
100 66 239 35 42 50 57 7
100 94 341 71 86 101 116 6
125 16 55 1 1 1 2 16
125 62 223 12 14 16 18 8
125 108 390 37 43 49 55 7
125 155 558 75 87 100 112 6
160 25 88 1 1 1 1 16
160 99 357 11 13 14 15 9
160 174 627 34 38 42 46 7
160 248 896 69 77 86 94 6
200 40 143 1 1 1 1 16
200 162 582 11 12 13 14 8
200 283 1020 33 36 40 43 7
200 405 1459 67 74 81 87 6
250 60 216 1 1 1 1 16
250 245 881 8 9 9 10 9
250 430 1547 23 25 28 30 7
250 614 2212 46 51 56 61 6
315 100 359 1 1 1 1 16
315 407 1464 5 6 7 7 8
315 713 2568 15 17 19 21 7
315 1020 3673 31 35 39 42 6
400 165 591 1 1 1 1 16
400 670 2413 4 5 5 6 8
400 1177 4236 12 14 15 16 7
400 1682 6058 25 27 30 33 6

① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm

Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – q v Extended
Attachments: BC0, BL0 **, BM0, BM0-J6

NS qv [l/s] qv [m³/h] Δpstmin [Pa] Δqv [±%]
100 10 34 1 1 1 2 16
100 46 165 17 20 24 28 8
100 83 297 54 65 77 88 6
100 118 428 111 135 158 182 5
125 16 55 1 1 1 2 16
125 75 270 18 21 24 27 8
125 134 484 57 66 75 84 6
125 194 699 117 137 156 175 5
160 25 88 1 1 1 1 16
160 120 433 17 18 20 22 8
160 216 777 52 58 64 71 6
160 311 1122 108 121 134 147 5
200 40 143 1 1 1 1 16
200 196 705 16 18 19 21 8
200 352 1266 51 56 61 66 6
200 507 1828 105 116 126 137 5
250 60 216 1 1 1 1 16
250 297 1068 11 12 13 15 8
250 533 1919 35 38 42 46 6
250 769 2771 72 80 87 95 5
315 100 359 1 1 1 1 16
315 493 1774 8 9 9 10 8
315 886 3188 24 26 29 32 6
315 1278 4603 49 55 60 66 5
400 165 591 1 1 1 1 16
400 812 2924 6 7 7 8 8
400 1461 5258 19 21 23 25 6
400 2108 7591 38 43 47 51 5

① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
** Control component to be discontinued - do not include in new projects

Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – qv standard
Attachments: BUDN, BUDNF, LN0, LK0, LB0, XB0, XB4, (B13 *, B1B *)

NS qv [l/s] qv [m³/h] Δpstmin [Pa] Δqv [±%]
100 10 34 1 1 1 2 16
100 39 141 12 15 18 20 9
100 69 247 37 45 53 61 7
100 98 354 76 92 109 125 6
125 16 55 1 1 1 2 16
125 64 229 13 15 17 19 8
125 112 404 40 46 52 59 7
125 160 578 80 94 107 120 6
160 25 88 1 1 1 1 16
160 102 368 12 13 15 16 8
160 180 648 36 41 45 49 7
160 257 928 74 83 92 101 6
200 40 143 1 1 1 1 16
200 166 599 12 13 14 15 8
200 293 1056 35 39 42 46 6
200 420 1512 72 79 86 94 6
250 60 216 1 1 1 1 16
250 252 908 8 9 10 11 8
250 444 1600 24 27 29 32 7
250 636 2292 49 55 60 65 6
315 100 359 1 1 1 1 16
315 419 1508 6 6 7 8 8
315 738 2658 17 19 20 22 6
315 1057 3807 33 37 42 46 6
400 165 591 1 1 1 1 16
400 691 2487 5 5 5 6 8
400 1218 4383 13 15 16 17 6
400 1744 6279 26 29 32 35 5

① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
* Control component has been discontinued

Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)

NS qv [l/s] qv [m³/h] Δpstmin [Pa] Δqv [±%]
100 14 50 2 2 3 3 14
100 42 151 14 17 20 23 8
100 70 253 39 47 56 64 7
100 98 354 76 92 109 125 6
125 23 81 2 2 3 3 13
125 69 247 15 18 20 22 8
125 114 412 41 48 54 61 6
125 160 578 80 94 107 120 6
160 36 129 2 2 2 2 14
160 110 395 14 15 17 19 8
160 184 662 38 42 47 51 7
160 257 928 74 83 92 101 6
200 59 210 2 2 2 2 13
200 179 644 13 15 16 17 8
200 299 1078 37 41 44 48 6
200 420 1512 72 79 86 94 6
250 89 318 1 2 2 2 14
250 271 976 9 10 11 12 8
250 454 1634 25 28 31 33 7
250 636 2292 49 55 60 65 6
315 147 529 1 1 1 1 13
315 451 1622 6 7 8 9 8
315 754 2714 17 19 21 23 6
315 1057 3807 33 37 42 46 6
400 242 871 1 1 1 1 13
400 743 2674 5 6 6 7 8
400 1243 4476 14 15 17 18 6
400 1744 6279 26 29 32 35 5

① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
* Control component has been discontinued

Quick sizing table for sound pressure levels

The quick sizing tables are based on generally accepted attenuation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.

Quick sizing table for air-regenerated noise L PA
Controller including silencer
(total flow rate range of type)

NS qv [l/s] qv [m³/h] 150 Pa 500 Pa
100 10 34 32 18 < 15 < 15 43 27 20 15
100 46 165 48 36 31 27 58 45 38 34
100 83 297 53 42 37 33 64 51 45 41
100 118 428 57 45 n.V. n.V. 67 55 49 45
125 16 55 34 19 < 15 < 15 46 30 23 18
125 75 270 47 36 31 28 59 46 41 37
125 134 484 52 42 37 34 63 52 47 43
125 194 699 53 44 n.V. n.V. 65 54 49 46
160 25 88 39 25 19 15 51 36 30 25
160 120 433 50 39 35 32 62 50 45 42
160 216 777 52 42 38 35 64 53 49 46
160 311 1122 53 44 40 37 65 55 51 47
200 40 143 41 30 24 20 51 41 36 31
200 196 705 50 42 38 36 61 52 48 44
200 352 1266 52 44 41 39 62 54 51 48
200 507 1828 52 46 43 41 63 56 52 50
250 60 216 41 32 26 23 51 41 37 33
250 297 1068 48 41 37 35 57 51 47 45
250 533 1919 49 43 40 38 58 53 50 47
250 769 2771 49 44 42 40 59 54 51 48
315 100 359 44 36 31 27 54 47 42 37
315 493 1774 49 42 39 36 60 53 49 46
315 886 3188 50 44 41 39 61 55 51 49
315 1278 4603 51 46 43 41 62 56 53 50
400 165 591 45 38 33 29 58 53 48 43
400 812 2924 46 40 36 34 59 54 50 47
400 1461 5258 46 41 38 36 60 55 51 48
400 2108 7591 47 42 40 39 60 55 52 49

Air-regenerated noise L PA [dB] at static differential pressure Δ pst 150 or 500 Pa

① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm

n.a.: The specified static differential pressure Δ pst is lower than the minimum differential pressure Δ pst min .

Quick sizing table for case-radiated noise L PA
Controller including acoustic cladding
(total flow rate range of type)

NS qv [l/s] qv [m³/h] 150 Pa 500 Pa
100 10 34 15 < 15 26 15
100 46 165 31 20 41 30
100 83 297 36 25 47 36
100 118 428 40 29 50 39
125 16 55 17 < 15 28 17
125 75 270 30 19 41 30
125 134 484 35 24 46 35
125 194 699 38 27 49 38
160 25 88 19 < 15 30 23
160 120 433 30 23 42 35
160 216 777 34 27 46 39
160 311 1122 37 30 48 41
200 40 143 21 < 15 31 16
200 196 705 32 17 42 27
200 352 1266 36 21 46 31
200 507 1828 39 24 49 34
250 60 216 25 < 15 34 19
250 297 1068 35 20 45 30
250 533 1919 39 24 48 33
250 769 2771 41 26 51 36
315 100 359 29 < 15 39 21
315 493 1774 40 22 50 32
315 886 3188 44 26 54 36
315 1278 4603 46 29 57 39
400 165 591 30 < 15 43 27
400 812 2924 39 23 52 36
400 1461 5258 42 26 55 39
400 2108 7591 44 28 57 41

Case-radiated noise L PA [dB] at static differential pressure Δ pst of 150 or 500 Pa

① Basic unit
② Basic unit with acoustic cladding

n.a.: The specified static differential pressure Δ pst is lower than the minimum differential pressure Δ pst min .

Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.

Circular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in 7 nominal sizes.

High control accuracy (even with upstream bend R = 1D).

Ready-to-commission unit which consists of the mechanical parts and the electronic control components Each unit contains an averaging effective pressure sensor for volume flow rate measurement, and a control damper blade. Factory mounted control components complete with wiring and tubing.

Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination.

Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed).

Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.

Special features

Materials and surfaces

Equivalence criteria

Technical data

Specification text for attachment

Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.

Sizing data

Life cycle assessment
A life cycle assessment is available for the product series in form of an Environmental Product Declaration (EPD) that has been checked and published by a programme holder.


Order code for volume flow control (with Easy attachment)
TVR D / 200 / D2 / Easy
| | | | |
1 2 5 6 7

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry required: None
D With acoustic cladding

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: without accessories
D2 Double lip seal both ends

7 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (w

Order example: TVR/200/D2/Easy

TypeTVR
Acoustic claddingWith acoustic cladding
Nominal size200 mm
AccessoriesDouble lip seal both ends
Attachments (control components)Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (by others)

,
Order code for volume flow control (with VARYCONTROL attachment)
TVR D A2 FL / 160 / G2 / TUNF/ RS / M/0 / UMZ/. / NC
| | | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11 12 13

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry required: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction

4 Duct connection

No entry: push-fit, suitable for ducts according toEN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]

100, 125, 160, 200, 250, 315, 400

6 Accessories

No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends

7 Attachments (control components)
For example
BC0 Compact controller
XD4 Universal controller (VARYCONTROL)

8 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract).


9 Operating mode
F Room master for single controller, constant setpoint value

M Room master for single controller, variable setpoint value
S Slave controller (only with room solutions)


10 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC

11 Expansion modules

Option 1: Power supply
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack for uninterruptible 230 V AC power supply (UPS)

Option 2: Digital communication interface
No entry: without communication interface
B With EM-BAC-MOD for VACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server

Option 3: Automatic zero point correction
No entry: no zero point correction
Z With EM-AUTOZERO solenoid valve for automatic zero point correction

12 Operating values for factory setting
Volume flow rate [m³/h or l/s]

For operating mode F
qᵥconst: constant volume flow rate1, 2

Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)

For operating mode M
qᵥmin: minimum volume flow rate1, 2
qᵥmax: maximum volume flow rate1, 2

Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)

For operating mode S
No parameters are required for the slave controller; all entries
have to be made on the room master

For volume flow rate operating values please note:
1 Single controller: qᵥmin, qᵥmax or qᵥconst apply to the controller
2 Room solutions: qᵥmin, qᵥmax, qᵥconst apply to the room
3 For more information on room solutions with several TROX
UNIVERSAL controllers connected with plug and play and for
order examples please refer to the product datasheet


13 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally Closed)

Usefull additions
Optional room control panel
BE-LCD with 40-character display

Order example: TVR/200/XD4/V2/500–1200 m³/h/NO

TypeTVR
Acoustic claddingWithout acoustic cladding
MaterialGalvanised sheet steel
Duct connectionPush-fit, suitable for ducts according to EN 1506, with groove for optional lip seal
Nominal size200
AccessoriesWithout accessories
Attachments (control components)VARYCONTROL Universal controller; static transducer; analogue control; safe position with spring return
Operating modeVariable operation
Signal voltage range2 – 10 V DC
Volume flow rate500 – 1200 [m³/h]
Damper blade positionPower off to open (Normally/ Open)

,
Order code for volume flow control (with TROX UNIVERSAL attachment)
TVR D A2 FL / 160 / G2 / TUNF / RS / M / 0 / UMZ / / NC
| | | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11 12 13

1 Type

TVR VAV terminal unit

2 Acoustic cladding
No entry required: None
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN
1506; with groove for optional lip seal
FL Flange both ends (not for TVR-D-P1)

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides

7 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)

8 Equipment function
Room control
RS Supply air control (Room Supply)
RE Extract air control (Room Extract)

9 Volume flow rate setting
M Master (RMF function) S Slave
F Constant flow rate controller

10 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC

11 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V
AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B
EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve

12 Operating values [m³/h or l/s] Master (RMF function) q ᵥmin : minimum volume flow rate q ᵥmax : maximum volume flow rate q ᵥconst_Supply air : constant supply air q ᵥconst_Extract air : constant extract air q ᵥDiff : Supply air/extract air difference Constant value q ᵥconst : constant volume flow rate SlaveNo entry required

13 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE

Useful additions
Room control panel
BE-LCD 40-character display

Order example: TVR-FL/250/TUNF/RE/M0/306-2205-0-0-0 [m³/h] /NC

TypeTVR
Acoustic claddingWithout acoustic cladding
MaterialGalvanised sheet steel
Duct connectionFlanges on both ends
Nominal size [mm]250
AccessoriesWithout accessories
Attachments (control components)TROX UNIVERSAL controller with spring return actuator (150s)
Equipment functionExtract air controller (Room Extract)
Operating modeRoom master or single controller, variable setpoint value
Signal voltage range0 – 10 V DC
Expansion modules24 V AC/DC supply, without digital communication interface, without automatic zero point correction
Operating values for factory settingqvmin = 306 m³/h
qvmax = 2205 m³/h
Damper blade positionPower off to close (Normally Closed)

Order code for differential pressure control (with VARYCONTROL attachment)

TVRDA2FL/160/G2/XF4/PDS/V/0/300-500 [Pa]/NO
| | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11 12

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends

7 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)

8 Equipment function/Installation location
PDS Duct pressure controller – supply air (Pressure Duct Supply)
PDE Duct pressure controller – extract air (Pressure Duct Extract)
PRS Room pressure controller – supply air (Pressure Room Supply)
PRE Room pressure controller – extract air (Pressure Room Extract)

9 Operating mode
F Constant value mode, one setpoint value (no externals switch conact)
V Variable operation (adjustable setpoint value range)

10 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC

11 Operating values for factory setting
Differential pressure [Pa]

For duct pressure control, enter the differential pressure [Pa] as an absolute value

pconst (with operating mode F)
pmin – ∆pmax (with operating mode V)

12 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally closed)

Order example 1: TVR-FL/250/G2/XF4/PDS/F0/450 [Pa]/NC

TypeTVR
Acoustic claddingWithout acoustic cladding
MaterialGalvanised sheet steel
Duct connectionFlanges on both ends
Nominal size [mm]250
AccessoriesMatching flanges for both ends
Attachments (control components)VARYCONTROL Universal controller for duct pressure; analogue interface
Equipment functionDuct pressure control, supply air (Pressure Duct Supply)
Operating modeConstant value mode
Signal voltage range0 – 10 V DC
Operating value450 [Pa]
Damper blade positionPower off to close (Normally Closed)

,
Order code for differential pressure control (with TROX UNIVERSAL controller as attachment)
TVR D FL / 160 / G2 / TUNF / PRS / MFP / 0 / UMZ / / NC
| | | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11 12 13

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends

7 Attachments (control components)
TROX UNIVERSAL controller with
TUN with actuator (150 s)
TUNF with spring return actuator (150 s)
TUS with fast-running actuator (3 s)
TUSD with fast-running actuator (3 s) and digital communication interface (TROX HPD)

8 Equipment function
PDS Duct pressure controller – supply air (Pressure Duct Supply)
PDE Duct pressure controller – extract air (Pressure Duct Extract)
PRS Room pressure controller – supply air (Pressure Room Supply)
PRE Room pressure controller – extract air (Pressure Room Extract)

9 Differential pressure setting
MFP Room master or single controller, constant pressure setpoint value
MVP Room master or single controller, variable pressure setpoint value

With room solutions
SFP Slave, constant pressure setpoint
SVP Slave, variable pressuure setpoint

10 Signal voltage range
For the actual and setpint value signals
0 0 – 10 V DC
2 2 – 10 V DC

11 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)

Option 2: Digital communication interface
No entry: without digital communication interface
B
With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server

Option 3: Volume flow rate measurement
No entry: without volume flow rate measurement
V With EM-V for volume flow rate measurement with the differential pressure controller

Option 4: Automatic zero point correction
No entry: no automatic zero pint correction
Z With EM-AUTOZERO solenoid valve for automatic zero pint correction (only togehter with EM-V)

12 Operating values for factory setting
Volume flow rate[m³/h or l/s], pressure [Pa]

For operating mode MFP or SFP
Δpconst: Constant differential pressure

For operating mode MVP or SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure

Other parameters for operating modes MFP and MVP
Only relevant for the room master as part of a room solution; for single controllers enter 0
qᵥmin: minimum volume flow rate (room value)
qᵥmax: maximum volume flow rate (room value)
qᵥconst_Supply air: constant supply air (room value)
qᵥconst_Extract air: constant extract air (room value)
qᵥDiff: Supply air/extract air difference (room value)

Please note
For more information on room solutions with several TROX UNIVERSAL controllers connected with plug and play and for order examples please refer to the product datasheet

13 Damper blade position

Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally Closed)

Useful additions
Differential pressure transducers required for room or duct pressure control have to be ordered separately or provided by others, e.g.
PT-699 Differential pressure transducer for room pressure control
PT-699-DUCT Differential pressure transducers for duct pressure control, including pressure measurement kit
Room control panel

Optional room control panel
BE-LCD
40-character display

Order example: TVR-D-FL/160/G2/TUNF/PRS/MFP/0/UMZ/250[Pa]/NC

TypeTVR
Acoustic claddingWithout acoustic cladding
MaterialGalvanised sheet steel
Duct connectionPush-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
Nominal size [mm]160
AccessoriesMatching flanges for both ends
Attachments (control components)TROX UNIVERSAL controller with fast-running actuator, analogue interface
Equipment functionRoom pressure contoller - supply air (Pressure Room Supply)
Operating modeRoom master or single controller, constant pressure setpoint value
Signal voltage range0 – 10 V DC
Expansion modulesWith EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)
With EM-BAC-MOD for Modbus RTU
Without volume flow rate measurement
With EM-AUTOZERO solenoid valve for automatic zero pint correction
Damper blade position250 [Pa]
Operating values for factory settingPower off to close (Normally Closed)

,
Order code for room control (with EASYLAB attachment)
TVRDFL/160/G2/ELAB/S/RS/UMZ/LAB/
| | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 11 12 13

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)

5 Nominal size [mm]

100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: none
D2 Double lip seal both ends
G2 Matching flanges on both ends

7 Attachments (control components)
ELAB EASYLAB controller TCU3

8 ActuatorsS Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital communication interface (TROX HPD)

9 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract)
PC Room pressure controller (Pressure Control)

11 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)

Option 2: Digital communication interface
No entry: none
B
With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server

Option 3: Automatic zero point correction
No entry: none
Z With EM-AUTOZERO solenoid valve for automatic zero point correction

12 Additional functions
Without room management function
LAB extract air led system (Laboratory)
CLR supply air led system (Clean Room)
With active room management function
LAB-RMF extract air led system (Laboratory) with room management function
CLR-RMF supply air led system (Clean Room) with room management function

13 Operating values
Volume flow rate [m³/h or l/s], Pressure [Pa]

Only required when room management function is active; total room extract air/supply air
q v1 : standard mode
q v2 : reduced operation
q v3 : increased operation
q v4 : constant supply air
q v5 : constant extract air
q v6 : Supply air/extract air difference
Δp Set : setpoint pressure (only with differential pressure control)

Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
Differential pressure transducers required for room pressure control have to be ordered separately or provided by others, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa

Order example: TVR-D-FL/200/D2/ELAB/SD/RS/MZ/LAB-RMF/2000/1500/2500/100/100/200

Acoustic claddingWith
Duct connectionFlanges on both ends
Materialgalvanised sheet steel
Nominal size200 mm
AccessoriesDouble lip seal both ends
Attachments (control components)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s) with digital communication interface (TROX HPD)
Equipment functionSupply air controller (Room Supply)
Expansion modulesExpansion modules EM-BAC-MOD for Modbus RTU and EM-AUTOZERO for automatic zero point correction
Additional functionRoom management function for extract air led system, e.g. laboratory
Operating valuesStandard mode = 2000 m³/h
Reduced operation = 1500 m³/h
Increased operation = 2500 m³/h
Constant supply air =100 m³/h
Constant extract air = 100 m³/h
supply air/extract air difference = 200 m³/h

,
Order code for single operation (with EASYLAB attachment)
TVRDFL/160/G2/ELAB/S/ECE0/UMZ/
| | | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11 13

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: none
D2 Double lip seal both sides'
G2 Matching flange on both ends

7 Attachments (control components)
ELAB EASYLAB controller TCU3

8 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital interface (TROX HPD)

9 Equipment function
Single operation
SC Supply controller – suplly air (Supply Controller)
EC Single controller – extract air (Extract Controller)

10 External volume flow rate setting
E0 Variable, signal voltage range 0 – 10 V DC
E2 Variable, signal voltage range 2 – 10 V DC
2P 2 switching steps (for one switch contact, by others)
3P 3 switching steps (for two switch contacts, by others)
F Constant value mode, one setpoint value (no external switch contact)

11 Expansion modules
Option 1: Power supply
No entry: 24 V AC/DC
T Witch EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)

Option 2: Digital communication interface
No entry: none
B
With EM-BAC-MOD for BACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) fpr BACnet IP, Modbus IP and web server

Option 3: Automatic zero point correction
No entry: none
Z With EM-AUTOZERO solenoid valve for automatic zero point correction

13 Operating values for factory setting
Volume flow rate [m³/h or l/s]


Order example: TVR-P1/100/ELAB/S/EC-2P/100/300

Acoustic claddingWithout
Duct connectionPush-fit
MaterialGalvanised sheet steel – surface powder-coated, RAL 7001, silver grey
Nominal size100 mm
AccessoriesWithout
Attachments (control components)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s)
Equipment functionSingle controller – extract air
Switch contacts for 2 volume flow rate values (by others)
Expansion modulesWithout
Operating valuesqv1 = 100 m³/h
qv2 = 300 m³/h

,
Order code for fume cupboard control (with EASYLAB attachment)
TVRDFL/160/G2/ELAB/S/FH – VS/UMZS/200 – 900 [m³/h]
| | | | | | | | | | |
1 2 3 4 5 6 7 8 9 10 11

1 Type
TVR VAV terminal unit

2 Acoustic cladding
No entry: none
D With acoustic cladding

3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction

4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories
No entry: none
D2 Double lip seal both ends
G2 Matching flanges on both ends

7 Attachments (control components)
ELAB EASYLAB controller TCU3

8 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital communication interface (TROX HPD)

9 Equipment function
Fume cupboard control
With face velocity transducer
FH-VS Fume cupboard control – control strategy based on face velocity ( with face velocity transducer)
With face velocity transducer and sash distance sensor
FH-VD Fume cupboard control – optimised control strategy based on face velocity (with face velocity transducer and sash distance sensor)
With sash distance sensor
FH-DS Fume cupboard control – linear control strategy (with sash distance sensor)
FH-DV Fume cupboard control Safety – safty optimised control strategy (with sash distance sensor)
With switch contacts (by others) for switching steps
FH-2P Fume cupboard control – 2 switching steps (for one switch contact, by others)
FH-3P Fume cupboard control – 3 switching steps (for two switch contacts, by others)
Without signalling
FH-F Fume cupboard control – Constant value mode (one setpoint value, no externals switch contacts)

10 Expansion modules
Option 1: Supply voltage
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack)for uninterruptible 230 V AC power supply (UPS)

Option 2: Digital communication interface
No entry: none
B
With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web servers

Option 3: Automatic zero point correction
No entry: none
Z Witch EM-AUTOZERO solenoid valve for automatic zero point correction

Option 4: Lighting
No entry: none
S With EM-LIGHT, wired socket for the connection of lighting and for switching the lighting on/off using the control panel (only with EM-TRF or EM-TRF-USV)

11 Operating values for factory setting
Volume flow rate [m³/h or l/s]

Depending on the equipment function
FH-VS: qvmin – qvmax
FH-VD: qvmin – qvmax
FH-DS: qvmin – qvmax
FH-DV: qvmin – qvmax
FH-2P: qv1/qv2
FH-3P: qv1/qv2/qv3
FH-F: qv1
Useful additions
Control panel for fume cupboard controllers, for displaying the functions of the control system according to EN 14175
BE-SEG-02 OLED display
BE-LCD 40-character display

Order example: TVR/200/D2/ELAB/FH-2P/TS/200 – 700

Acoustic claddingWithout
Nominal size200 mm
Duct connectionPush-fit
AccessoriesDouble lip seal both ends
Attachments (control components)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s)
Equipment functionFume cupboard control with 2 switching steps (for one switch contact, by others)
Expansion modulesWith expansion module EM-TRF, transformer for 230 V AC mains supply
with expansion module EM-LIGHT for the connection of lighting and for switching the lighting on/off using the control panel on the fume cupboard controller
Operating valuesqv1 = 200 m³/hqv2 = 700 m³/h