VAV terminal unit type TVR with an Easy controller
Easy controller, Compact controllerEasy controller, Compact controller
VAV terminal unit, variant TVR-D-FLConstruction with acoustic cladding and flange
Universal controller (VARYCONTROL)
TROX UNIVERSAL controller,
TROX LABCONTROL controller
Conforms to VDI 6022
Optional equipment and accessories
Application
Special features
Nominal sizes
Construction
Parts and characteristics
Attachments
Accessories
Useful additions
Construction features
Materials and surfaces
Galvanised sheet steel construction
Powder-coated construction (P1)
Stainless steel construction (A2)
Variant with acoustic cladding (-D)
Standards and guidelines
Fulfils the hygiene requirements of
Closed blade air leakage:
Maintenance
Schematic illustration of the TVR
① Effective pressure sensor
③ Double lip seal
④ Control components, e.g. an Easy controller
The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate. The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL). For most applications, the setpoint value comes from a room temperature controller. The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.
Nominal sizes | 100 – 400 mm |
Volume flow rate range | 34 – 7591 m³/h or 10 – 2108 l/s |
Volume flow rate control range (unit for dynamic effective pressure measurements) | Approx. 10 – 100% of the nominal volume flow rate |
Volume flow rate control range (unit for static effective pressure measurements) | Approx. 15 to 100% of the nominal volume flow rate |
Minimum differential pressure |
Up to 117 Pa (without circular silencer)
Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.
The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".
Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates q vmin and q vmax .
Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. Sufficient static differential pressure (Δ pstat,min ) must be ensured for all operating conditions and for all controllers . The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.
Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – Easy (potentiometers)
Attachment: Easy
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |||
---|---|---|---|---|---|---|---|
① | ② | ③ | ④ | ||||
100 | 10 | 34 | 1 | 1 | 1 | 2 | 16 |
100 | 38 | 136 | 12 | 14 | 16 | 19 | 9 |
100 | 66 | 239 | 35 | 42 | 50 | 57 | 7 |
100 | 94 | 341 | 71 | 86 | 101 | 116 | 6 |
125 | 16 | 55 | 1 | 1 | 1 | 2 | 16 |
125 | 62 | 223 | 12 | 14 | 16 | 18 | 8 |
125 | 108 | 390 | 37 | 43 | 49 | 55 | 7 |
125 | 155 | 558 | 75 | 87 | 100 | 112 | 6 |
160 | 25 | 88 | 1 | 1 | 1 | 1 | 16 |
160 | 99 | 357 | 11 | 13 | 14 | 15 | 9 |
160 | 174 | 627 | 34 | 38 | 42 | 46 | 7 |
160 | 248 | 896 | 69 | 77 | 86 | 94 | 6 |
200 | 40 | 143 | 1 | 1 | 1 | 1 | 16 |
200 | 162 | 582 | 11 | 12 | 13 | 14 | 8 |
200 | 283 | 1020 | 33 | 36 | 40 | 43 | 7 |
200 | 405 | 1459 | 67 | 74 | 81 | 87 | 6 |
250 | 60 | 216 | 1 | 1 | 1 | 1 | 16 |
250 | 245 | 881 | 8 | 9 | 9 | 10 | 9 |
250 | 430 | 1547 | 23 | 25 | 28 | 30 | 7 |
250 | 614 | 2212 | 46 | 51 | 56 | 61 | 6 |
315 | 100 | 359 | 1 | 1 | 1 | 1 | 16 |
315 | 407 | 1464 | 5 | 6 | 7 | 7 | 8 |
315 | 713 | 2568 | 15 | 17 | 19 | 21 | 7 |
315 | 1020 | 3673 | 31 | 35 | 39 | 42 | 6 |
400 | 165 | 591 | 1 | 1 | 1 | 1 | 16 |
400 | 670 | 2413 | 4 | 5 | 5 | 6 | 8 |
400 | 1177 | 4236 | 12 | 14 | 15 | 16 | 7 |
400 | 1682 | 6058 | 25 | 27 | 30 | 33 | 6 |
① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – q v Extended
Attachments: BC0, BL0 **, BM0, BM0-J6
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |||
---|---|---|---|---|---|---|---|
① | ② | ③ | ④ | ||||
100 | 10 | 34 | 1 | 1 | 1 | 2 | 16 |
100 | 46 | 165 | 17 | 20 | 24 | 28 | 8 |
100 | 83 | 297 | 54 | 65 | 77 | 88 | 6 |
100 | 118 | 428 | 111 | 135 | 158 | 182 | 5 |
125 | 16 | 55 | 1 | 1 | 1 | 2 | 16 |
125 | 75 | 270 | 18 | 21 | 24 | 27 | 8 |
125 | 134 | 484 | 57 | 66 | 75 | 84 | 6 |
125 | 194 | 699 | 117 | 137 | 156 | 175 | 5 |
160 | 25 | 88 | 1 | 1 | 1 | 1 | 16 |
160 | 120 | 433 | 17 | 18 | 20 | 22 | 8 |
160 | 216 | 777 | 52 | 58 | 64 | 71 | 6 |
160 | 311 | 1122 | 108 | 121 | 134 | 147 | 5 |
200 | 40 | 143 | 1 | 1 | 1 | 1 | 16 |
200 | 196 | 705 | 16 | 18 | 19 | 21 | 8 |
200 | 352 | 1266 | 51 | 56 | 61 | 66 | 6 |
200 | 507 | 1828 | 105 | 116 | 126 | 137 | 5 |
250 | 60 | 216 | 1 | 1 | 1 | 1 | 16 |
250 | 297 | 1068 | 11 | 12 | 13 | 15 | 8 |
250 | 533 | 1919 | 35 | 38 | 42 | 46 | 6 |
250 | 769 | 2771 | 72 | 80 | 87 | 95 | 5 |
315 | 100 | 359 | 1 | 1 | 1 | 1 | 16 |
315 | 493 | 1774 | 8 | 9 | 9 | 10 | 8 |
315 | 886 | 3188 | 24 | 26 | 29 | 32 | 6 |
315 | 1278 | 4603 | 49 | 55 | 60 | 66 | 5 |
400 | 165 | 591 | 1 | 1 | 1 | 1 | 16 |
400 | 812 | 2924 | 6 | 7 | 7 | 8 | 8 |
400 | 1461 | 5258 | 19 | 21 | 23 | 25 | 6 |
400 | 2108 | 7591 | 38 | 43 | 47 | 51 | 5 |
① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
** Control component to be discontinued - do not include in new projects
Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – qv standard
Attachments: BUDN, BUDNF, LN0, LK0, LB0, XB0, XB4, (B13 *, B1B *)
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |||
---|---|---|---|---|---|---|---|
① | ② | ③ | ④ | ||||
100 | 10 | 34 | 1 | 1 | 1 | 2 | 16 |
100 | 39 | 141 | 12 | 15 | 18 | 20 | 9 |
100 | 69 | 247 | 37 | 45 | 53 | 61 | 7 |
100 | 98 | 354 | 76 | 92 | 109 | 125 | 6 |
125 | 16 | 55 | 1 | 1 | 1 | 2 | 16 |
125 | 64 | 229 | 13 | 15 | 17 | 19 | 8 |
125 | 112 | 404 | 40 | 46 | 52 | 59 | 7 |
125 | 160 | 578 | 80 | 94 | 107 | 120 | 6 |
160 | 25 | 88 | 1 | 1 | 1 | 1 | 16 |
160 | 102 | 368 | 12 | 13 | 15 | 16 | 8 |
160 | 180 | 648 | 36 | 41 | 45 | 49 | 7 |
160 | 257 | 928 | 74 | 83 | 92 | 101 | 6 |
200 | 40 | 143 | 1 | 1 | 1 | 1 | 16 |
200 | 166 | 599 | 12 | 13 | 14 | 15 | 8 |
200 | 293 | 1056 | 35 | 39 | 42 | 46 | 6 |
200 | 420 | 1512 | 72 | 79 | 86 | 94 | 6 |
250 | 60 | 216 | 1 | 1 | 1 | 1 | 16 |
250 | 252 | 908 | 8 | 9 | 10 | 11 | 8 |
250 | 444 | 1600 | 24 | 27 | 29 | 32 | 7 |
250 | 636 | 2292 | 49 | 55 | 60 | 65 | 6 |
315 | 100 | 359 | 1 | 1 | 1 | 1 | 16 |
315 | 419 | 1508 | 6 | 6 | 7 | 8 | 8 |
315 | 738 | 2658 | 17 | 19 | 20 | 22 | 6 |
315 | 1057 | 3807 | 33 | 37 | 42 | 46 | 6 |
400 | 165 | 591 | 1 | 1 | 1 | 1 | 16 |
400 | 691 | 2487 | 5 | 5 | 5 | 6 | 8 |
400 | 1218 | 4383 | 13 | 15 | 16 | 17 | 6 |
400 | 1744 | 6279 | 26 | 29 | 32 | 35 | 5 |
① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
* Control component has been discontinued
Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle
Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)
NS | qv [l/s] | qv [m³/h] | Δpstmin [Pa] | Δqv [±%] | |||
---|---|---|---|---|---|---|---|
① | ② | ③ | ④ | ||||
100 | 14 | 50 | 2 | 2 | 3 | 3 | 14 |
100 | 42 | 151 | 14 | 17 | 20 | 23 | 8 |
100 | 70 | 253 | 39 | 47 | 56 | 64 | 7 |
100 | 98 | 354 | 76 | 92 | 109 | 125 | 6 |
125 | 23 | 81 | 2 | 2 | 3 | 3 | 13 |
125 | 69 | 247 | 15 | 18 | 20 | 22 | 8 |
125 | 114 | 412 | 41 | 48 | 54 | 61 | 6 |
125 | 160 | 578 | 80 | 94 | 107 | 120 | 6 |
160 | 36 | 129 | 2 | 2 | 2 | 2 | 14 |
160 | 110 | 395 | 14 | 15 | 17 | 19 | 8 |
160 | 184 | 662 | 38 | 42 | 47 | 51 | 7 |
160 | 257 | 928 | 74 | 83 | 92 | 101 | 6 |
200 | 59 | 210 | 2 | 2 | 2 | 2 | 13 |
200 | 179 | 644 | 13 | 15 | 16 | 17 | 8 |
200 | 299 | 1078 | 37 | 41 | 44 | 48 | 6 |
200 | 420 | 1512 | 72 | 79 | 86 | 94 | 6 |
250 | 89 | 318 | 1 | 2 | 2 | 2 | 14 |
250 | 271 | 976 | 9 | 10 | 11 | 12 | 8 |
250 | 454 | 1634 | 25 | 28 | 31 | 33 | 7 |
250 | 636 | 2292 | 49 | 55 | 60 | 65 | 6 |
315 | 147 | 529 | 1 | 1 | 1 | 1 | 13 |
315 | 451 | 1622 | 6 | 7 | 8 | 9 | 8 |
315 | 754 | 2714 | 17 | 19 | 21 | 23 | 6 |
315 | 1057 | 3807 | 33 | 37 | 42 | 46 | 6 |
400 | 242 | 871 | 1 | 1 | 1 | 1 | 13 |
400 | 743 | 2674 | 5 | 6 | 6 | 7 | 8 |
400 | 1243 | 4476 | 14 | 15 | 17 | 18 | 6 |
400 | 1744 | 6279 | 26 | 29 | 32 | 35 | 5 |
① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
* Control component has been discontinued
Quick sizing table for sound pressure levels
The quick sizing tables are based on generally accepted attenuation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.
Quick sizing table for air-regenerated noise L PA
Controller including silencer
(total flow rate range of type)
NS | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa | ||||||
---|---|---|---|---|---|---|---|---|---|---|
① | ② | ③ | ④ | ① | ② | ③ | ④ | |||
100 | 10 | 34 | 32 | 18 | < 15 | < 15 | 43 | 27 | 20 | 15 |
100 | 46 | 165 | 48 | 36 | 31 | 27 | 58 | 45 | 38 | 34 |
100 | 83 | 297 | 53 | 42 | 37 | 33 | 64 | 51 | 45 | 41 |
100 | 118 | 428 | 57 | 45 | n.V. | n.V. | 67 | 55 | 49 | 45 |
125 | 16 | 55 | 34 | 19 | < 15 | < 15 | 46 | 30 | 23 | 18 |
125 | 75 | 270 | 47 | 36 | 31 | 28 | 59 | 46 | 41 | 37 |
125 | 134 | 484 | 52 | 42 | 37 | 34 | 63 | 52 | 47 | 43 |
125 | 194 | 699 | 53 | 44 | n.V. | n.V. | 65 | 54 | 49 | 46 |
160 | 25 | 88 | 39 | 25 | 19 | 15 | 51 | 36 | 30 | 25 |
160 | 120 | 433 | 50 | 39 | 35 | 32 | 62 | 50 | 45 | 42 |
160 | 216 | 777 | 52 | 42 | 38 | 35 | 64 | 53 | 49 | 46 |
160 | 311 | 1122 | 53 | 44 | 40 | 37 | 65 | 55 | 51 | 47 |
200 | 40 | 143 | 41 | 30 | 24 | 20 | 51 | 41 | 36 | 31 |
200 | 196 | 705 | 50 | 42 | 38 | 36 | 61 | 52 | 48 | 44 |
200 | 352 | 1266 | 52 | 44 | 41 | 39 | 62 | 54 | 51 | 48 |
200 | 507 | 1828 | 52 | 46 | 43 | 41 | 63 | 56 | 52 | 50 |
250 | 60 | 216 | 41 | 32 | 26 | 23 | 51 | 41 | 37 | 33 |
250 | 297 | 1068 | 48 | 41 | 37 | 35 | 57 | 51 | 47 | 45 |
250 | 533 | 1919 | 49 | 43 | 40 | 38 | 58 | 53 | 50 | 47 |
250 | 769 | 2771 | 49 | 44 | 42 | 40 | 59 | 54 | 51 | 48 |
315 | 100 | 359 | 44 | 36 | 31 | 27 | 54 | 47 | 42 | 37 |
315 | 493 | 1774 | 49 | 42 | 39 | 36 | 60 | 53 | 49 | 46 |
315 | 886 | 3188 | 50 | 44 | 41 | 39 | 61 | 55 | 51 | 49 |
315 | 1278 | 4603 | 51 | 46 | 43 | 41 | 62 | 56 | 53 | 50 |
400 | 165 | 591 | 45 | 38 | 33 | 29 | 58 | 53 | 48 | 43 |
400 | 812 | 2924 | 46 | 40 | 36 | 34 | 59 | 54 | 50 | 47 |
400 | 1461 | 5258 | 46 | 41 | 38 | 36 | 60 | 55 | 51 | 48 |
400 | 2108 | 7591 | 47 | 42 | 40 | 39 | 60 | 55 | 52 | 49 |
Air-regenerated noise L PA [dB] at static differential pressure Δ pst 150 or 500 Pa
① Basic unit
② Basic unit with circular silencer CF, insulation thickness 50 mm, length 500 mm
③ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1000 mm
④ Basic unit with circular silencer CF, insulation thickness 50 mm, length 1500 mm
n.a.: The specified static differential pressure Δ pst is lower than the minimum differential pressure Δ pst min .
Quick sizing table for case-radiated noise L PA
Controller including acoustic cladding
(total flow rate range of type)
NS | qv [l/s] | qv [m³/h] | 150 Pa | 500 Pa | ||
---|---|---|---|---|---|---|
① | ② | ① | ② | |||
100 | 10 | 34 | 15 | < 15 | 26 | 15 |
100 | 46 | 165 | 31 | 20 | 41 | 30 |
100 | 83 | 297 | 36 | 25 | 47 | 36 |
100 | 118 | 428 | 40 | 29 | 50 | 39 |
125 | 16 | 55 | 17 | < 15 | 28 | 17 |
125 | 75 | 270 | 30 | 19 | 41 | 30 |
125 | 134 | 484 | 35 | 24 | 46 | 35 |
125 | 194 | 699 | 38 | 27 | 49 | 38 |
160 | 25 | 88 | 19 | < 15 | 30 | 23 |
160 | 120 | 433 | 30 | 23 | 42 | 35 |
160 | 216 | 777 | 34 | 27 | 46 | 39 |
160 | 311 | 1122 | 37 | 30 | 48 | 41 |
200 | 40 | 143 | 21 | < 15 | 31 | 16 |
200 | 196 | 705 | 32 | 17 | 42 | 27 |
200 | 352 | 1266 | 36 | 21 | 46 | 31 |
200 | 507 | 1828 | 39 | 24 | 49 | 34 |
250 | 60 | 216 | 25 | < 15 | 34 | 19 |
250 | 297 | 1068 | 35 | 20 | 45 | 30 |
250 | 533 | 1919 | 39 | 24 | 48 | 33 |
250 | 769 | 2771 | 41 | 26 | 51 | 36 |
315 | 100 | 359 | 29 | < 15 | 39 | 21 |
315 | 493 | 1774 | 40 | 22 | 50 | 32 |
315 | 886 | 3188 | 44 | 26 | 54 | 36 |
315 | 1278 | 4603 | 46 | 29 | 57 | 39 |
400 | 165 | 591 | 30 | < 15 | 43 | 27 |
400 | 812 | 2924 | 39 | 23 | 52 | 36 |
400 | 1461 | 5258 | 42 | 26 | 55 | 39 |
400 | 2108 | 7591 | 44 | 28 | 57 | 41 |
Case-radiated noise L PA [dB] at static differential pressure Δ pst of 150 or 500 Pa
① Basic unit
② Basic unit with acoustic cladding
n.a.: The specified static differential pressure Δ pst is lower than the minimum differential pressure Δ pst min .
Note:
Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.
Circular VAV terminal units for variable and constant air volume systems, suitable for supply or extract air, available in 7 nominal sizes.
High control accuracy (even with upstream bend R = 1D).
Ready-to-commission unit which consists of the mechanical parts and the electronic control components Each unit contains an averaging effective pressure sensor for volume flow rate measurement, and a control damper blade. Factory mounted control components complete with wiring and tubing.
Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination.
Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed).
Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.
Special features
Materials and surfaces
Equivalence criteria
Technical data
Specification text for attachment
Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.
Sizing data
Life cycle assessment
A life cycle assessment is available for the product series in form of an Environmental Product Declaration (EPD) that has been checked and published by a programme holder.
TVR | – | D | / | 200 | / | D2 | / | Easy |
| | | | | | | | | | ||||
1 | 2 | 5 | 6 | 7 |
1 Type
TVR VAV terminal unit
2 Acoustic cladding
No entry required: None
D With acoustic cladding
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends
7 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (w
Order example: TVR/200/D2/Easy
Type | TVR |
Acoustic cladding | With acoustic cladding |
Nominal size | 200 mm |
Accessories | Double lip seal both ends |
Attachments (control components) | Volume flow controller, dynamic, analogue interface, setting of qvmin and qvmax with potentiometers (by others) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | . | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | ||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
1 Type
TVR VAV terminal unit
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry required: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according toEN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends
7 Attachments (control components)
For example
BC0 Compact controller
XD4 Universal controller (VARYCONTROL)
8 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract).
9 Operating mode
F Room master for single controller, constant setpoint value
M Room master for single controller, variable setpoint value
S Slave controller (only with room solutions)
10 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion modules
Option 1: Power supply
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: without communication interface
B With EM-BAC-MOD for VACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Automatic zero point correction
No entry: no zero point correction
Z With EM-AUTOZERO solenoid valve for automatic zero point correction
12 Operating values for factory setting
Volume flow rate [m³/h or l/s]
For operating mode F
qᵥconst: constant volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode M
qᵥmin: minimum volume flow rate1, 2
qᵥmax: maximum volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode S
No parameters are required for the slave controller; all entries
have to be made on the room master
For volume flow rate operating values please note:
1 Single controller: qᵥmin, qᵥmax or qᵥconst apply to the controller
2 Room solutions: qᵥmin, qᵥmax, qᵥconst apply to the room
3 For more information on room solutions with several TROX
UNIVERSAL controllers connected with plug and play and for
order examples please refer to the product datasheet
13 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally Closed)
Usefull additions
Optional room control panel
BE-LCD with 40-character display
Order example: TVR/200/XD4/V2/500–1200 m³/h/NO
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Push-fit, suitable for ducts according to EN 1506, with groove for optional lip seal |
Nominal size | 200 |
Accessories | Without accessories |
Attachments (control components) | VARYCONTROL Universal controller; static transducer; analogue control; safe position with spring return |
Operating mode | Variable operation |
Signal voltage range | 2 – 10 V DC |
Volume flow rate | 500 – 1200 [m³/h] |
Damper blade position | Power off to open (Normally/ Open) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | ||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
TVR VAV terminal unit
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN
1506; with groove for optional lip seal
FL Flange both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
8 Equipment function
Room control
RS Supply air control (Room Supply)
RE Extract air control (Room Extract)
9 Volume flow rate setting
M Master (RMF function) S Slave
F Constant flow rate controller
10 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V
AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
12 Operating values [m³/h or l/s] Master (RMF function) q ᵥmin : minimum volume flow rate q ᵥmax : maximum volume flow rate q ᵥconst_Supply air : constant supply air q ᵥconst_Extract air : constant extract air q ᵥDiff : Supply air/extract air difference Constant value q ᵥconst : constant volume flow rate SlaveNo entry required
13 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Order example: TVR-FL/250/TUNF/RE/M0/306-2205-0-0-0 [m³/h] /NC
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Without accessories |
Attachments (control components) | TROX UNIVERSAL controller with spring return actuator (150s) |
Equipment function | Extract air controller (Room Extract) |
Operating mode | Room master or single controller, variable setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | 24 V AC/DC supply, without digital communication interface, without automatic zero point correction |
Operating values for factory setting | qvmin = 306 m³/h qvmax = 2205 m³/h |
Damper blade position | Power off to close (Normally Closed) |
Order code for differential pressure control (with VARYCONTROL attachment)
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | XF4 | / | PDS | / | V | / | 0 | / | 300-500 [Pa] | / | NO |
| | | | | | | | | | | | | | | | | | | | | | | | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
1 Type
TVR VAV terminal unit
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends
7 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
8 Equipment function/Installation location
PDS Duct pressure controller – supply air (Pressure Duct Supply)
PDE Duct pressure controller – extract air (Pressure Duct Extract)
PRS Room pressure controller – supply air (Pressure Room Supply)
PRE Room pressure controller – extract air (Pressure Room Extract)
9 Operating mode
F Constant value mode, one setpoint value (no externals switch conact)
V Variable operation (adjustable setpoint value range)
10 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
11 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value
∆pconst (with operating mode F)
∆pmin – ∆pmax (with operating mode V)
12 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally closed)
Order example 1: TVR-FL/250/G2/XF4/PDS/F0/450 [Pa]/NC
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Matching flanges for both ends |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure; analogue interface |
Equipment function | Duct pressure control, supply air (Pressure Duct Supply) |
Operating mode | Constant value mode |
Signal voltage range | 0 – 10 V DC |
Operating value | 450 [Pa] |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
| | | | | | | | | | | | | | | | | | | | | | | | | | ||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN with actuator (150 s)
TUNF with spring return actuator (150 s)
TUS with fast-running actuator (3 s)
TUSD with fast-running actuator (3 s) and digital communication interface (TROX HPD)
8 Equipment function
PDS Duct pressure controller – supply air (Pressure Duct Supply)
PDE Duct pressure controller – extract air (Pressure Duct Extract)
PRS Room pressure controller – supply air (Pressure Room Supply)
PRE Room pressure controller – extract air (Pressure Room Extract)
9 Differential pressure setting
MFP Room master or single controller, constant pressure setpoint value
MVP Room master or single controller, variable pressure setpoint value
With room solutions
SFP Slave, constant pressure setpoint
SVP Slave, variable pressuure setpoint
10 Signal voltage range
For the actual and setpint value signals
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: without digital communication interface
B With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Volume flow rate measurement
No entry: without volume flow rate measurement
V With EM-V for volume flow rate measurement with the differential pressure controller
Option 4: Automatic zero point correction
No entry: no automatic zero pint correction
Z With EM-AUTOZERO solenoid valve for automatic zero pint correction (only togehter with EM-V)
12 Operating values for factory setting
Volume flow rate[m³/h or l/s], pressure [Pa]
For operating mode MFP or SFP
Δpconst: Constant differential pressure
For operating mode MVP or SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure
Other parameters for operating modes MFP and MVP
Only relevant for the room master as part of a room solution; for single controllers enter 0
qᵥmin: minimum volume flow rate (room value)
qᵥmax: maximum volume flow rate (room value)
qᵥconst_Supply air: constant supply air (room value)
qᵥconst_Extract air: constant extract air (room value)
qᵥDiff: Supply air/extract air difference (room value)
Please note
For more information on room solutions with several TROX UNIVERSAL controllers connected with plug and play and for order examples please refer to the product datasheet
13 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally Closed)
Useful additions
Differential pressure transducers required for room or duct pressure control have to be ordered separately or provided by others, e.g.
PT-699 Differential pressure transducer for room pressure control
PT-699-DUCT Differential pressure transducers for duct pressure control, including pressure measurement kit
Room control panel
Optional room control panel
BE-LCD 40-character display
Order example: TVR-D-FL/160/G2/TUNF/PRS/MFP/0/UMZ/250[Pa]/NC
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal |
Nominal size [mm] | 160 |
Accessories | Matching flanges for both ends |
Attachments (control components) | TROX UNIVERSAL controller with fast-running actuator, analogue interface |
Equipment function | Room pressure contoller - supply air (Pressure Room Supply) |
Operating mode | Room master or single controller, constant pressure setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS) With EM-BAC-MOD for Modbus RTU Without volume flow rate measurement With EM-AUTOZERO solenoid valve for automatic zero pint correction |
Damper blade position | 250 [Pa] |
Operating values for factory setting | Power off to close (Normally Closed) |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 11 | 12 | 13 |
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: none
D2 Double lip seal both ends
G2 Matching flanges on both ends
7 Attachments (control components)
ELAB EASYLAB controller TCU3
8 ActuatorsS Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital communication interface (TROX HPD)
9 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract)
PC Room pressure controller (Pressure Control)
11 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: none
B With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Automatic zero point correction
No entry: none
Z With EM-AUTOZERO solenoid valve for automatic zero point correction
12 Additional functions
Without room management function
LAB extract air led system (Laboratory)
CLR supply air led system (Clean Room)
With active room management function
LAB-RMF extract air led system (Laboratory) with room management function
CLR-RMF supply air led system (Clean Room) with room management function
13 Operating values
Volume flow rate [m³/h or l/s], Pressure [Pa]
Only required when room management function is active; total room extract air/supply air
q v1 : standard mode
q v2 : reduced operation
q v3 : increased operation
q v4 : constant supply air
q v5 : constant extract air
q v6 : Supply air/extract air difference
Δp Set : setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
Differential pressure transducers required for room pressure control have to be ordered separately or provided by others, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Order example: TVR-D-FL/200/D2/ELAB/SD/RS/MZ/LAB-RMF/2000/1500/2500/100/100/200
Acoustic cladding | With |
Duct connection | Flanges on both ends |
Material | galvanised sheet steel |
Nominal size | 200 mm |
Accessories | Double lip seal both ends |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) with digital communication interface (TROX HPD) |
Equipment function | Supply air controller (Room Supply) |
Expansion modules | Expansion modules EM-BAC-MOD for Modbus RTU and EM-AUTOZERO for automatic zero point correction |
Additional function | Room management function for extract air led system, e.g. laboratory |
Operating values | Standard mode = 2000 m³/h Reduced operation = 1500 m³/h Increased operation = 2500 m³/h Constant supply air =100 m³/h Constant extract air = 100 m³/h supply air/extract air difference = 200 m³/h |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | ELAB | / | S | / | EC | – | E0 | / | UMZ | / | … |
| | | | | | | | | | | | | | | | | | | | | | | | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 13 |
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: none
D2 Double lip seal both sides'
G2 Matching flange on both ends
7 Attachments (control components)
ELAB EASYLAB controller TCU3
8 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital interface (TROX HPD)
9 Equipment function
Single operation
SC Supply controller – suplly air (Supply Controller)
EC Single controller – extract air (Extract Controller)
10 External volume flow rate setting
E0 Variable, signal voltage range 0 – 10 V DC
E2 Variable, signal voltage range 2 – 10 V DC
2P 2 switching steps (for one switch contact, by others)
3P 3 switching steps (for two switch contacts, by others)
F Constant value mode, one setpoint value (no external switch contact)
11 Expansion modules
Option 1: Power supply
No entry: 24 V AC/DC
T Witch EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: none
B With EM-BAC-MOD for BACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) fpr BACnet IP, Modbus IP and web server
Option 3: Automatic zero point correction
No entry: none
Z With EM-AUTOZERO solenoid valve for automatic zero point correction
13 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Order example: TVR-P1/100/ELAB/S/EC-2P/100/300
Acoustic cladding | Without |
Duct connection | Push-fit |
Material | Galvanised sheet steel – surface powder-coated, RAL 7001, silver grey |
Nominal size | 100 mm |
Accessories | Without |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Single controller – extract air Switch contacts for 2 volume flow rate values (by others) |
Expansion modules | Without |
Operating values | qv1 = 100 m³/h qv2 = 300 m³/h |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | ELAB | / | S | / | FH – VS | / | UMZS | / | 200 – 900 [m³/h] |
| | | | | | | | | | | | | | | | | | | | | | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 |
1 Type
TVR VAV terminal unit
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001 (silver grey)
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: none
D2 Double lip seal both ends
G2 Matching flanges on both ends
7 Attachments (control components)
ELAB EASYLAB controller TCU3
8 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s) with digital communication interface (TROX HPD)
9 Equipment function
Fume cupboard control
With face velocity transducer
FH-VS Fume cupboard control – control strategy based on face velocity ( with face velocity transducer)
With face velocity transducer and sash distance sensor
FH-VD Fume cupboard control – optimised control strategy based on face velocity (with face velocity transducer and sash distance sensor)
With sash distance sensor
FH-DS Fume cupboard control – linear control strategy (with sash distance sensor)
FH-DV Fume cupboard control Safety – safty optimised control strategy (with sash distance sensor)
With switch contacts (by others) for switching steps
FH-2P Fume cupboard control – 2 switching steps (for one switch contact, by others)
FH-3P Fume cupboard control – 3 switching steps (for two switch contacts, by others)
Without signalling
FH-F Fume cupboard control – Constant value mode (one setpoint value, no externals switch contacts)
10 Expansion modules
Option 1: Supply voltage
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack)for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: none
B With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web servers
Option 3: Automatic zero point correction
No entry: none
Z Witch EM-AUTOZERO solenoid valve for automatic zero point correction
Option 4: Lighting
No entry: none
S With EM-LIGHT, wired socket for the connection of lighting and for switching the lighting on/off using the control panel (only with EM-TRF or EM-TRF-USV)
11 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Depending on the equipment function
FH-VS: qvmin – qvmax
FH-VD: qvmin – qvmax
FH-DS: qvmin – qvmax
FH-DV: qvmin – qvmax
FH-2P: qv1/qv2
FH-3P: qv1/qv2/qv3
FH-F: qv1
Useful additions
Control panel for fume cupboard controllers, for displaying the functions of the control system according to EN 14175
BE-SEG-02 OLED display
BE-LCD 40-character display
Order example: TVR/200/D2/ELAB/FH-2P/TS/200 – 700
Acoustic cladding | Without |
Nominal size | 200 mm |
Duct connection | Push-fit |
Accessories | Double lip seal both ends |
Attachments (control components) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Fume cupboard control with 2 switching steps (for one switch contact, by others) |
Expansion modules | With expansion module EM-TRF, transformer for 230 V AC mains supply with expansion module EM-LIGHT for the connection of lighting and for switching the lighting on/off using the control panel on the fume cupboard controller |
Operating values | qv1 = 200 m³/hqv2 = 700 m³/h |